Standard
BS EN 50618:2014; EN 60228
Construction
Conductor : BS EN 60228, Class 5 flexible tinned copper
Insulation : Halogen-free cross-linked compound, White colored
Sheath : Halogen-free cross-linked, flame retardant compound
Specification
Voltage rating
DC: 1.5 kV DC
AC: 1.0/1.0kV AC
Temperature rating
The cables are designed to operate at a normal maximum conductor temperature of 90oC, but for a maximum of 20 000 hours a max. conductor temperature of 120oC at a max. ambient temperature of 90oC is permitted.
Minimum bending radius
OD: overall diameter of cable
-Fixed : 4OD
-Flexed : 5OD
Test voltage
DC voltage: 15kVdc/5minutes
AC voltage: 6.5kVac/5minutes
Cable marking
Printed on sheath surface with 550mm interval: " EN 50618 H1Z2Z2-K (or H1Z2Z2-K/AT) 1x[SIZE] SQMM SOLAR XLPO - 1500V DC* (Mnf. Year) * LS-VINA Cable & System "
Optional
- Sheath color: Black or Back with Red strip or as request.
- Anti-termite additive in over sheath.
Features
UV resistant
Flame retardant to IEC 60332-1-2
Halogen free accordance with BS EN 50525-1
Low smoke density accordance with IEC 61034-2
Number and nominal cross sectional area of conductors
|
Thickness of insulation Specified value
(1)
|
Thickness of sheath Specified value
(2)
|
Mean overall diameter Upper limit Informative value
|
Maximum DC resistance of conductor at 20oC
|
Maximum insulation resistance
|
Approx.Overall diameter of cable
|
Approx.Overall weight of cable
|
at 20oC
|
at 90oC
|
mm2
|
mm
|
mm
|
mm
|
Ω/km
|
MΩ.km
|
MΩ.km
|
mm
|
kg/km
|
2.5 |
0.7 |
0.8 |
5.9 |
8.21 |
690 |
0.69 |
5.7 |
50 |
4 |
0.7 |
0.8 |
6.6 |
5.09 |
580 |
0.58 |
6.2 |
70 |
6 |
0.7 |
0.8 |
7.4 |
3.39 |
500 |
0.50 |
6.8 |
90 |
10 |
0.7 |
0.8 |
8.8 |
1.95 |
420 |
0.42 |
7.7 |
130 |
16 |
0.7 |
0.9 |
10.1 |
1.24 |
340 |
0.34 |
9.5 |
205 |
25 |
0.9 |
1.0 |
12.5 |
0.795 |
340 |
0.34 |
11.4 |
305 |
35 |
0.9 |
1.1 |
14.0 |
0.565 |
290 |
0.29 |
12.8 |
405 |
50 |
1.0 |
1.2 |
16.3 |
0.393 |
270 |
0.27 |
14.9 |
565 |
70 |
1.1 |
1.2 |
18.7 |
0.277 |
250 |
0.25 |
17.2 |
800 |
95 |
1.1 |
1.3 |
20.8 |
0.210 |
220 |
0.22 |
18.9 |
1010 |
120 |
1.2 |
1.3 |
22.8 |
0.164 |
210 |
0.21 |
21.0 |
1290 |
150 |
1.4 |
1.4 |
25.5 |
0.132 |
210 |
0.21 |
23.3 |
1590 |
185 |
1.6 |
1.6 |
28.5 |
0.108 |
200 |
0.20 |
25.9 |
1930 |
240 |
1.7 |
1.7 |
32.1 |
0.082 |
200 |
0.20 |
29.3 |
2560 |
1 : The smallest value measured shall not be fall below 90% of the specified value by more than 0.1 mm
2 : The smallest value measured shall not be fall below 85% of the specified value by more than 0.1 mm