Applied standard
IEC 60502-1:2009
Construction / Materials
Rate voltage : 0.6/1(1.2)kV
Insulation : Type XLPE
Number of conductor : 2 core
Nominal Area | Diameter conductor | Nominal thickness insulation | Thickness Inner sheath | Diameter Wire Armour | Thickness tape armor | Nominal Thickness Outer sheath | Approx. Overall Cable Diameter | Approx. Weight Copper conductor | Approx. Weight Aluminium conductor | Nominal Drum Length |
| | | GSWA | DSTA | GSWA | DSTA | UnAr | GSWA | DSTA | UnAr | GSWA | DSTA | UnAr | GSWA | DSTA | UnAr | GSWA | DSTA | UnAr | GSWA | DSTA |
mm2 | mm | mm | mm | mm | mm | mm | mm | mm | mm | mm | mm | mm | kg/km | kg/km | kg/km | kg/km | kg/km | kg/km | m | m | m |
1.5 | 1.56 | 0.7 | 1.0 | - | 0.9 | - | 1.8 | 1.8 | - | 11 | 15 | - | 130 | 360 | - | - | - | - | 2,000 | 2,000 | - |
2.5 | 2.01 | 0.7 | 1.0 | - | 0.9 | - | 1.8 | 1.8 | - | 12 | 15 | - | 170 | 430 | - | - | - | - | 2,000 | 2,000 | - |
4 | 2.55 | 0.7 | 1.0 | 1.0 | 0.9 | 0.2 | 1.8 | 1.8 | 1.8 | 13 | 16 | 15 | 210 | 500 | 320 | - | - | - | 2,000 | 2,000 | 2,000 |
6 | 3.12 | 0.7 | 1.0 | 1.0 | 0.9 | 0.2 | 1.8 | 1.8 | 1.8 | 14 | 17 | 16 | 280 | 570 | 390 | - | - | - | 2,000 | 2,000 | 2,000 |
10 | 4.05 | 0.7 | 1.0 | 1.0 | 1.25 | 0.2 | 1.8 | 1.8 | 1.8 | 16 | 20 | 18 | 370 | 740 | 500 | - | - | - | 2,000 | 2,000 | 2,000 |
16 | 4.65 | 0.7 | 1.0 | 1.0 | 1.25 | 0.2 | 1.8 | 1.8 | 1.8 | 17 | 21 | 19 | 460 | 940 | 640 | 270 | 740 | 460 | 2,000 | 2,000 | 2,000 |
25 | 5.9 | 0.9 | 1.0 | 1.0 | 1.6 | 0.2 | 1.8 | 1.8 | 1.8 | 21 | 26 | 24 | 690 | 1,390 | 920 | 380 | 1,080 | 620 | 2,000 | 2,000 | 2,000 |
35 | 6.9 | 0.9 | 1.0 | 1.0 | 1.6 | 0.2 | 1.8 | 1.8 | 1.8 | 23 | 28 | 26 | 900 | 1,670 | 1,150 | 470 | 1,240 | 730 | 2,000 | 1,500 | 1,500 |
50 | 8.0 | 1.0 | 1.0 | 1.0 | 1.6 | 0.2 | 1.8 | 1.8 | 1.8 | 26 | 31 | 29 | 1,170 | 2,050 | 1,470 | 610 | 1,480 | 900 | 2,000 | 1,500 | 1,500 |
70 | 9.8 | 1.1 | 1.0 | 1.0 | 1.6 | 0.2 | 1.8 | 2.0 | 1.9 | 29 | 35 | 33 | 1,630 | 2,670 | 1,990 | 800 | 1,840 | 1,150 | 1,500 | 1,000 | 1,000 |
95 | 11.4 | 1.1 | 1.2 | 1.2 | 2.0 | 0.2 | 2.0 | 2.1 | 2.0 | 33 | 40 | 37 | 2,200 | 3,660 | 2,620 | 1,040 | 2,500 | 1,460 | 1,500 | 500 | 1,000 |
120 | 12.8 | 1.2 | 1.2 | 1.2 | 2.0 | 0.5 | 2.1 | 2.2 | 2.2 | 37 | 43 | 43 | 2,740 | 4,330 | 3,600 | 1,280 | 2,870 | 2,130 | 1,000 | 500 | 500 |
150 | 14.2 | 1.4 | 1.2 | 1.2 | 2.0 | 0.5 | 2.2 | 2.3 | 2.3 | 41 | 47 | 47 | 3,390 | 5,130 | 4,340 | 1,580 | 3,320 | 2,520 | 500 | 500 | 500 |
185 | 15.8 | 1.6 | 1.4 | 1.4 | 2.5 | 0.5 | 2.3 | 2.5 | 2.4 | 45 | 53 | 52 | 4,220 | 6,680 | 5,320 | 1,940 | 4,410 | 3,040 | 500 | 500 | 500 |
240 | 18.1 | 1.7 | 1.4 | 1.4 | 2.5 | 0.5 | 2.5 | 2.7 | 2.6 | 51 | 59 | 58 | 5,480 | 8,230 | 6,730 | 2,500 | 5,240 | 3,740 | 500 | 500 | 300 |
300 | 20.4 | 1.8 | 1.6 | 1.6 | 2.5 | 0.5 | 2.7 | 2.8 | 2.8 | 57 | 65 | 63 | 6,790 | 9,870 | 8,210 | 3,030 | 6,110 | 4,450 | 500 | 500 | 300 |
400 | 23.2 | 2.0 | 1.6 | 1.6 | 2.5 | 0.5 | 2.9 | 3.1 | 3.0 | 63 | 71 | 70 | 8,700 | 12,150 | 10,300 | 3,900 | 7,380 | 5,510 | 300 | 300 | 250 |
UnAr = Unarmoured; GSWA = Galvanized Steel Wire Armoured; DSTA = Double Steel Tape Armoured; 16mm2 ~ 400mm2 conductors are circular strand compacted