Construction
(1)Conductor: 7 stranded wires
(2)Insulation: Type PVC/A
Applied standard
IEC 60502-1 : 2009
Maximum conductor temperature in normal use: 70oC
Voltage test : 3.5 kV/5 minutes
Application
For fixed wiring
No of core & Nominal cross section area | Construction of conductor (Number/ diameter of wire) | Conductor Approx Diameter | Maximum DC resistance of conductor at 20oC | Insulation thickness (Aver.value value) | Minimum insulation resistance at 70oC | Calculated overall diameter of cable | Approx . overall weight of cable | Standard packing length per each coil |
No.x mm2 | No./mm | mm | Ω/km | mm | MΩ.km | mm | kg/km | m |
1x1.5 | 7 / 0.52 | 1.56 | 12.10 | 0.8 | 0.0124 | 3.4 | 25 | 300 |
1x2.5 | 7 / 0.67 | 2.01 | 7.410 | 0.8 | 0.0102 | 3.8 | 35 | 300 |
1x4 | 7 / 0.85 | 2.55 | 4.610 | 1.0 | 0.0099 | 4.8 | 55 | 300 |
1x6 | 7 / 1.04 | 3.12 | 3.080 | 1.0 | 0.0085 | 5.3 | 75 | 200 |
1x10 | 7 / 1.35 | 4.05 | 1.830 | 1.0 | 0.0069 | 6.3 | 120 | 100 |