Applied standard
AS/NZS 1429.1:2006
Properties
Rated voltage : 12.7/22(24)kV
AC Voltage Test : 42kV / 5min.
Partial Discharge : 5pC/19kV
Insulation resistance : Min. 40,000 GΩm(20oC)
Copper wire screen earth fault current : 10kA/s
Bending radius
During installation: 25xOD
Installed: 15xOD
(OD: overall diameter)
CUSTOMER’S OPTIONS
Water-blocking
- Longitudinal water-blocking: Swellable tape
- Radial water-blocking: Aluminum laminated tape
Protection from insect attack
- Chemical add in to over sheath
- Polyamide jacket
- Double brass tape
AS/NZS 1429.1:2006
12.7/22(24)kV - Single core
Nominal Area | Diameter Conductor | Nominal thickness insulation | Copper wire screened structure | Nominal Thickness of composite sheath | Approx. Overall Cable Diameter | Approx. Weight of conductor (copper or aluminum conductors) |
| | | | | |
PVC | HDPE | CU | AL |
mm2 | mm | mm | no./mm | mm | mm | mm | Kg/km | Kg/km |
35 | 6.90 | 5.5 | 48 / 1.35 | 1.0 | 1.0 | 28 | 1,430 | - |
50 | 8.00 | 5.5 | 48 / 1.35 | 1.0 | 1.0 | 29 | 1,570 | - |
70 | 9.70 | 5.5 | 48 / 1.35 | 1.0 | 1.0 | 30 | 1,800 | 1,390 |
95 | 11.4 | 5.5 | 48 / 1.35 | 1.0 | 1.0 | 32 | 2,080 | 1,510 |
120 | 12.8 | 5.5 | 48 / 1.35 | 1.0 | 1.0 | 33 | 2,340 | 1,610 |
150 | 14.2 | 5.5 | 48 / 1.35 | 1.0 | 1.0 | 35 | 2,620 | 1,720 |
185 | 15.8 | 5.5 | 48 / 1.35 | 1.0 | 1.1 | 37 | 3,010 | 1,880 |
240 | 18.1 | 5.5 | 48 / 1.35 | 1.1 | 1.1 | 39 | 3,600 | 2,130 |
300 | 20.4 | 5.5 | 48 / 1.35 | 1.1 | 1.1 | 42 | 4,210 | 2,350 |
400 | 23.2 | 5.5 | 48 / 1.35 | 1.2 | 1.2 | 45 | 5,080 | 2,700 |
500 | 26.3 | 5.5 | 48 / 1.35 | 1.2 | 1.2 | 49 | 6,230 | 3,170 |
630 | 30.2 | 5.5 | 48 / 1.35 | 1.3 | 1.3 | 54 | 7,680 | 3,720 |
800 | 34.2 | 5.5 | 48 / 1.35 | 1.3 | 1.4 | 58 | 9,410 | 4,330 |