Applied standard
AS/NZS 1429.1:2006
Properties
Rated voltage : 12.7/22(24)kV
AC Voltage Test : 42kV / 5min.
Partial Discharge : 5pC/19kV
Insulation resistance : Min. 40,000 GΩm(20oC)
Copper wire screen earth fault current : 10kA/s
Bending radius
During installation: 25xOD
Installed: 15xOD
(OD: overall diameter)
CUSTOMER’S OPTIONS
Water-blocking
- Longitudinal water-blocking: Swellable tape
- Radial water-blocking: Aluminum laminated tape
Protection from insect attack
- Chemical add in to over sheath
- Polyamide jacket
- Double brass tape
AS/NZS 1429.1:2006
12.7/22(24)kV - Single core
Nominal Area
|
Diameter Conductor
|
Nominal thickness insulation
|
Copper wire screened structure
|
Nominal Thickness of composite sheath
|
Approx. Overall Cable Diameter
|
Approx. Weight of conductor (copper or aluminum conductors)
|
|
|
|
|
|
PVC
|
HDPE
|
CU
|
AL
|
mm2
|
mm
|
mm
|
no./mm
|
mm
|
mm
|
mm
|
Kg/km
|
Kg/km
|
35
|
6.90
|
5.5
|
48 / 1.35
|
1.0
|
1.0
|
28
|
1,430
|
-
|
50
|
8.00
|
5.5
|
48 / 1.35
|
1.0
|
1.0
|
29
|
1,570
|
-
|
70
|
9.70
|
5.5
|
48 / 1.35
|
1.0
|
1.0
|
30
|
1,800
|
1,390
|
95
|
11.4
|
5.5
|
48 / 1.35
|
1.0
|
1.0
|
32
|
2,080
|
1,510
|
120
|
12.8
|
5.5
|
48 / 1.35
|
1.0
|
1.0
|
33
|
2,340
|
1,610
|
150
|
14.2
|
5.5
|
48 / 1.35
|
1.0
|
1.0
|
35
|
2,620
|
1,720
|
185
|
15.8
|
5.5
|
48 / 1.35
|
1.0
|
1.1
|
37
|
3,010
|
1,880
|
240
|
18.1
|
5.5
|
48 / 1.35
|
1.1
|
1.1
|
39
|
3,600
|
2,130
|
300
|
20.4
|
5.5
|
48 / 1.35
|
1.1
|
1.1
|
42
|
4,210
|
2,350
|
400
|
23.2
|
5.5
|
48 / 1.35
|
1.2
|
1.2
|
45
|
5,080
|
2,700
|
500
|
26.3
|
5.5
|
48 / 1.35
|
1.2
|
1.2
|
49
|
6,230
|
3,170
|
630
|
30.2
|
5.5
|
48 / 1.35
|
1.3
|
1.3
|
54
|
7,680
|
3,720
|
800
|
34.2
|
5.5
|
48 / 1.35
|
1.3
|
1.4
|
58
|
9,410
|
4,330
|