Applied standard
AS/NZS 1429.1:2006
Properties
Rated voltage : 12.7/22(24)kV
AC Voltage Test : 42kV / 5min.
Partial Discharge : 5pC/19kV
Insulation resistance : Min. 40,000 GΩm(20oC)
Copper wire screen earth fault current : 10kA/s
Bending radius
During installation: 25xOD
Installed: 15xOD
(OD: overall diameter)
CUSTOMER’S OPTIONS
Water-blocking
- Longitudinal water-blocking: Swellable tape
- Radial water-blocking: Aluminum laminated tape
Protection from insect attack
- Chemical add in to over sheath
- Polyamide jacket
- Double brass tape
AS/NZS 1429.1:2006
12.7/22(24)kV, Three-core
Nominal Area | Diameter conductor | Nominal thickness insulation | Copper wire screened structure | Nominal Thickness of composite sheath | Approx. Overall Cable Diameter | Approx. Weight of conductor (copper or aluminum conductors) |
| | | | | |
PVC | HDPE | CU | AL |
mm2 | mm | mm | no./mm | mm | mm | mm | Kg/km | Kg/km |
25 | 5.9 | 5.5 | 40 / 0.85 | 1.3 | 1.3 | 51 | 2,930 | - |
35 | 6.9 | 5.5 | 40 / 0.85 | 1.3 | 1.4 | 54 | 3,350 | - |
50 | 8.0 | 5.5 | 40 / 0.85 | 1.4 | 1.4 | 56 | 3,790 | - |
70 | 9.7 | 5.5 | 40 / 0.85 | 1.4 | 1.5 | 60 | 4,580 | 3,340 |
95 | 11.4 | 5.5 | 40 / 0.85 | 1.5 | 1.5 | 64 | 5,520 | 3,770 |
120 | 12.8 | 5.5 | 40 / 0.85 | 1.5 | 1.6 | 67 | 6,380 | 4,180 |
150 | 14.2 | 5.5 | 40 / 0.85 | 1.6 | 1.6 | 70 | 7,340 | 4,620 |
185 | 15.8 | 5.5 | 40 / 0.85 | 1.6 | 1.7 | 74 | 8,560 | 5,150 |
240 | 18.1 | 5.5 | 40 / 0.85 | 1.7 | 1.8 | 80 | 10,530 | 6,050 |
300 | 20.4 | 5.5 | 40 / 0.85 | 1.8 | 1.9 | 85 | 12,570 | 6,940 |
400 | 23.2 | 5.5 | 40 / 0.85 | 1.9 | 2.0 | 92 | 15,330 | 8,130a |