Applied standard
AS/NZS 1429.1:2006
Properties
Rated voltage : 19/33(36)kV
AC Voltage Test : 63kV / 5min.
Partial Discharge : 5pC/29kV
Insulation resistance : Min. 40,000 GΩm(20oC)
Copper wire screen earth fault current : 10kA/s
Bending radius
During installation: 25xOD
Installed: 15xOD
(OD: overall diameter)
CUSTOMER’S OPTIONS
Water-blocking
- Longitudinal water-blocking: Swellable tape
- Radial water-blocking: Aluminum laminated tape
Protection from insect attack
- Chemical add in to over sheath
- Polyamide jacket
- Double brass tape
AS/NZS 1429.1:2006
19/33(36)kV - Single core
Nominal Area | Diameter conductor | Nominal thickness insulation | Copper wire screened structure | Nominal Thickness of composite sheath | Approx. Overall Cable Diameter | Approx. Weight of conductor (copper or aluminum conductors) |
| | | | | |
PVC | HDPE | CU | AL |
mm2 | mm | mm | no./mm | mm | mm | mm | Kg/km | Kg/km |
35 | 6.90 | 8.0 | 48 / 1.35 | 1.0 | 1.0 | 33 | 1,660 | - |
50 | 8.00 | 8.0 | 48 / 1.35 | 1.0 | 1.0 | 34 | 1,810 | - |
70 | 9.70 | 8.0 | 48 / 1.35 | 1.0 | 1.1 | 36 | 2,060 | 1,650 |
95 | 11.4 | 8.0 | 48 / 1.35 | 1.0 | 1.1 | 38 | 2,360 | 1,780 |
120 | 12.8 | 8.0 | 48 / 1.35 | 1.1 | 1.1 | 39 | 2,640 | 1,910 |
150 | 14.2 | 8.0 | 48 / 1.35 | 1.1 | 1.1 | 41 | 2,930 | 2,040 |
185 | 15.8 | 8.0 | 48 / 1.35 | 1.1 | 1.2 | 42 | 3,340 | 2,210 |
240 | 18.1 | 8.0 | 48 / 1.35 | 1.1 | 1.2 | 45 | 3,930 | 2,450 |
300 | 20.4 | 8.0 | 48 / 1.35 | 1.2 | 1.2 | 47 | 4,570 | 2,710 |
400 | 23.2 | 8.0 | 48 / 1.35 | 1.2 | 1.3 | 50 | 5,450 | 3,070 |
500 | 26.3 | 8.0 | 48 / 1.35 | 1.3 | 1.3 | 55 | 6,630 | 3,570 |
630 | 30.2 | 8.0 | 48 / 1.35 | 1.3 | 1.4 | 59 | 8,090 | 4,130 |
800 | 34.2 | 8.0 | 48 / 1.35 | 1.4 | 1.5 | 63 | 9,890 | 4,800 |