Applied standard
AS/NZS 1429.1:2006
Properties
Rated voltage: 19/33(36)kV
AC Voltage Test : 21kV / 5min.
Partial Discharge: 5pC/10kV
Insulation resistance: Min. 40,000 GΩm(20oC)
Copper wire screen earth fault current: 10kA/s
Bending radius
During installation: 25xOD
Installed: 15xOD
(OD: overall diameter)
CUSTOMER’S OPTIONS
Water-blocking
- Longitudinal water-blocking: Swellable tape
- Radial water-blocking: Aluminum laminated tape
Protection from insect attack
- Chemical add in to over sheath
- Polyamide jacket
- Double brass tape
AS/NZS 1429.1:2006
19/33(36)kV - Three-core
Nominal Area | Diameter conductor | Nominal thickness insulation | Copper wire screened structure | Nominal Thickness of composite sheath | Approx. Overall Cable Diameter | Approx. Weight of conductor (copper or aluminum conductors) |
| | | | |
PVC | HDPE | CU | AL |
mm2 | mm | mm | no./mm | mm | mm | mm | Kg/km | Kg/km |
35 | 6.9 | 8.0 | 40 / 0.85 | 1.5 | 1.6 | 65 | 4,200 | - |
50 | 8.0 | 8.0 | 40 / 0.85 | 1.6 | 1.6 | 68 | 4,740 | - |
70 | 9.7 | 8.0 | 40 / 0.85 | 1.6 | 1.7 | 72 | 5,580 | 4,340 |
95 | 11.4 | 8.0 | 40 / 0.85 | 1.7 | 1.7 | 76 | 6,560 | 4,820 |
120 | 12.8 | 8.0 | 40 / 0.85 | 1.7 | 1.8 | 79 | 7,460 | 5,260 |
150 | 14.2 | 8.0 | 40 / 0.85 | 1.8 | 1.8 | 82 | 8,460 | 5,750 |
185 | 15.8 | 8.0 | 40 / 0.85 | 1.8 | 1.9 | 86 | 9,800 | 6,390 |
240 | 18.1 | 8.0 | 40 / 0.85 | 1.9 | 2.0 | 92 | 11,840 | 7,360 |
300 | 20.4 | 8.0 | 40 / 0.85 | 2.0 | 2.0 | 97 | 13,920 | 8,280 |
400 | 23.2 | 8.0 | 40 / 0.85 | 2.1 | 2.2 | 103 | 16,850 | 9,650 |