Construction
(1)Conductor: multi-wires stranded
(2)Insulation: Type PVC/D
Assembly: The cores shall be laid parallel
(3)Over sheath: PVC compound Type ST5
Applied standard
IEC 60227-5 (Model IEC 53)
Maximum conductor temperature in normal use: 70oC
Voltage test : arcording to insulation thickness
1500V/5 minutes up to and including 0.6mm
2000V/5 minutes exceed 0.6mm
Core color :
No of core & Nominal cross section area | Maximum diameter of wire in conductor | Conductor Approx. Diameter | Maximum DC resistance of conductor at 20oC | Insulation Thickness (specified value) | Over sheath Thickness (specified value) | Minimum insulation resistance at 70oC | Mean overall diameter of cord | Calculated overall diameter of cord | Approx . overall weight of cable | Standard packing length per each coil |
Lower limit | Upper limit |
No.xmm2 | mm | mm | Ω/km | mm | mm | MΩ.km | mm | mm | mm | Kg/km | m |
2x0.75 | 0.21 | 1.1 | 26.0 | 0.6 | 0.8 | 0.0110 | 3.7x6.0 | 4.5x7.2 | 4.3x6.8 | 50 | 200 |
2x1.0 | 0.21 | 1.3 | 19.5 | 0.6 | 0.8 | 0.0100 | 3.9x6.2 | 4.7x7.5 | 4.5x7.2 | 57 | 200 |
2x1.5 | 0.26 | 1.6 | 13.3 | 0.7 | 0.8 | 0.0100 | 4.4x7.0 | 5.3x8.50 | 5.0x8.2 | 75 | 200 |
2x2.5 | 0.26 | 2.0 | 7.98 | 0.8 | 1.0 | 0.0090 | 5.1x8.4 | 6.2x10.1 | 6.0x9.8 | 114 | 100 |
2x4 | 0.31 | 2.6 | 4.95 | 0.8 | 1.2 | 0.0070 | 5.7x9.5 | 6.9x11.5 | 6.8x11.2 | 158 | 100 |
2x6 | 0.31 | 3.2 | 3.30 | 0.8 | 1.2 | 0.0067 | 6.4x10.8 | 7.8x13.0 | 7.6x12.6 | 213 | 100 |