Construction
(1)Conductor: multi-wires stranded
(2)Insulation: Type PVC/D
Assembly: The cores shall be laid parallel
(3)Over sheath: PVC compound Type ST5
Applied standard
IEC 60227-5 (Model IEC 53)
Maximum conductor temperature in normal use: 70oC
Voltage test : arcording to insulation thickness
1500V/5 minutes up to and including 0.6mm
2000V/5 minutes exceed 0.6mm
Core color : 
No of core & Nominal cross section area
|
Maximum diameter of wire in conductor
|
Conductor Approx. Diameter
|
Maximum DC resistance of conductor at 20oC
|
Insulation Thickness (specified value)
|
Over sheath Thickness (specified value)
|
Minimum insulation resistance at 70oC
|
Mean overall diameter of cord |
Calculated overall diameter of cord
|
Approx . overall weight of cable
|
Standard packing length per each coil
|
Lower limit
|
Upper limit
|
No.xmm2
|
mm
|
mm
|
Ω/km
|
mm
|
mm
|
MΩ.km
|
mm
|
mm
|
mm
|
Kg/km
|
m
|
2x0.75
|
0.21
|
1.1
|
26.0
|
0.6
|
0.8
|
0.0110
|
3.7x6.0
|
4.5x7.2
|
4.3x6.8
|
50
|
200
|
2x1.0
|
0.21
|
1.3
|
19.5
|
0.6
|
0.8
|
0.0100
|
3.9x6.2
|
4.7x7.5
|
4.5x7.2
|
57
|
200
|
2x1.5
|
0.26
|
1.6
|
13.3
|
0.7
|
0.8
|
0.0100
|
4.4x7.0
|
5.3x8.50
|
5.0x8.2
|
75
|
200
|
2x2.5
|
0.26
|
2.0
|
7.98
|
0.8
|
1.0
|
0.0090
|
5.1x8.4
|
6.2x10.1
|
6.0x9.8
|
114
|
100
|
2x4
|
0.31
|
2.6
|
4.95
|
0.8
|
1.2
|
0.0070
|
5.7x9.5
|
6.9x11.5
|
6.8x11.2
|
158
|
100
|
2x6
|
0.31
|
3.2
|
3.30
|
0.8
|
1.2
|
0.0067
|
6.4x10.8
|
7.8x13.0
|
7.6x12.6
|
213
|
100
|