Construction
(1)Conductor: Solid wire
(2)Insulation: PVC/C
Applied standard
IEC 60227 -3 (Model IEC 01 )
Maximum conductor temperature in normal use: 70oC
Voltage test : 2500V/5 minutes
Color : 
No of core & Nominal cross section area
|
Construction of conductor (Number/diameter of wire)
|
Conductor Approx. Diameter
|
Maximum DC resistance of conductor at 20oC
|
Insulation Thickness (specified value)
|
Minimum insulation resistance at 70oC
|
Mean overall diameter of cable |
Calculated overall diameter of cable
|
Approx . overall weight of cable
|
Standard packing length per each coil
|
Lower limit
|
Upper limit
|
No.xmm2
|
No./mm
|
mm
|
Ω/km
|
mm
|
MΩ.km
|
mm
|
mm
|
mm
|
Kg/km
|
m
|
1x1.5
|
1/1.38
|
1.38
|
12.10
|
0.7
|
0.0110
|
2.6
|
3.2
|
3.0
|
22
|
300
|
1x2.5
|
1/1.78
|
1.78
|
7.410
|
0.8
|
0.0100
|
3.2
|
3.9
|
3.6
|
34
|
300
|
1x4
|
1/2.25
|
2.25
|
4.610
|
0.8
|
0.0085
|
3.8
|
4.6
|
4.1
|
49
|
300
|
1x6
|
1/2.75
|
2.75
|
3.080
|
0.8
|
0.0070
|
4.3
|
5.2
|
4.6
|
69
|
200
|