Construction
(1)Conductor: 7 stranded wires
(2)Insulation: PVC/C
Applied standard
IEC 60227 -3 (Model IEC 01)
Maximum conductor temperature in normal use: 70oC
Voltage test : 2500V/5 minutes
Color :
Application
For fixed wiring
No of core & Nominal cross section area | Construction of conductor (Number/ diameter of wire) | Conductor Approx. Diameter | Maximum DC resistance of conductor at 20oC | Insulation Thickness (specified value) | Minimum insulation resistance at 70oC | Mean overall diameter of cable | Calculated overall diameter of cable | Approx. overall weight of cable | Standard packing length per each coil |
Lower limit | Upper limit |
No.xmm2 | No./mm | mm | Ω/km | mm | MΩ.km | mm | mm | mm | Kg/km | m |
1x1.5 | 7/0.52 | 1.56 | 12.10 | 0.7 | 0.0100 | 2.7 | 3.3 | 3.2 | 22 | 300 |
1x2.5 | 7/0.67 | 2.01 | 7.410 | 0.8 | 0.0090 | 3.3 | 4.0 | 3.8 | 35 | 300 |
1x4 | 7/0.85 | 2.55 | 4.610 | 0.8 | 0.0077 | 3.8 | 4.6 | 4.4 | 50 | 300 |
1x6 | 7/1.04 | 3.12 | 3.080 | 0.8 | 0.0065 | 4.3 | 5.2 | 4.9 | 70 | 200 |
1x10 | 7/1.35 | 4.05 | 1.830 | 1.0 | 0.0065 | 5.6 | 6.7 | 6.3 | 120 | 100 |