Construction
(1)Conductor: 7 stranded wires
(2)Insulation: PVC/C
Applied standard
IEC 60227 -3 (Model IEC 01)
Maximum conductor temperature in normal use: 70oC
Voltage test : 2500V/5 minutes
Color : 
Application
For fixed wiring
No of core & Nominal cross section area
|
Construction of conductor (Number/ diameter of wire)
|
Conductor Approx. Diameter
|
Maximum DC resistance of conductor at 20oC
|
Insulation Thickness (specified value)
|
Minimum insulation resistance at 70oC
|
Mean overall diameter of cable |
Calculated overall diameter of cable
|
Approx. overall weight of cable
|
Standard packing length per each coil
|
Lower limit
|
Upper limit
|
No.xmm2
|
No./mm
|
mm
|
Ω/km
|
mm
|
MΩ.km
|
mm
|
mm
|
mm
|
Kg/km
|
m
|
1x1.5
|
7/0.52
|
1.56
|
12.10
|
0.7
|
0.0100
|
2.7
|
3.3
|
3.2
|
22
|
300
|
1x2.5
|
7/0.67
|
2.01
|
7.410
|
0.8
|
0.0090
|
3.3
|
4.0
|
3.8
|
35
|
300
|
1x4
|
7/0.85
|
2.55
|
4.610
|
0.8
|
0.0077
|
3.8
|
4.6
|
4.4
|
50
|
300
|
1x6
|
7/1.04
|
3.12
|
3.080
|
0.8
|
0.0065
|
4.3
|
5.2
|
4.9
|
70
|
200
|
1x10
|
7/1.35
|
4.05
|
1.830
|
1.0
|
0.0065
|
5.6
|
6.7
|
6.3
|
120
|
100
|