Construction
(1)Conductor: Multi-wire stranded
(2)Insulation: PVC/C
Applied standard
IEC 60227 -3 (Model IEC 02)
Maximum conductor temperature in normal use: 70oC
Voltage test : 2500V/5 minutes
Color : 
Application
For fixed wiring
No of core & Nominal cross section area
|
Maximum diameter of wire in conductor
|
Conductor Approx. Diameter
|
Maximum DC resistance of conductor at 20oC
|
Insulation Thickness (specified value)
|
Minimum insulation resistance at 70oC
|
Mean overall diameter of cable |
Calculated overall diameter of cable
|
Approx . overall weight of cable
|
Standard packing length per each coil
|
Lower limit
|
Upper limit
|
No.xmm2
|
No./mm
|
mm
|
Ω/km
|
mm
|
MΩ.km
|
mm
|
mm
|
mm
|
Kg/km
|
m
|
1x1.5
|
0.26
|
1.6
|
13.3
|
0.7
|
0.010
|
2.8
|
3.4
|
3.2
|
23
|
300
|
1x2.5
|
0.26
|
2.0
|
7.98
|
0.8
|
0.009
|
3.4
|
4.1
|
3.8
|
35
|
300
|
1x4
|
0.31
|
2.6
|
4.95
|
0.8
|
0.007
|
3.9
|
4.8
|
4.4
|
51
|
300
|
1x6
|
0.31
|
3.2
|
3.30
|
0.8
|
0.006
|
4.4
|
5.3
|
5.0
|
72
|
200
|