Applied standard
AS/NZS 1429.1:2006
Properties
Rated voltage : 6.35/11(12)kV
AC Voltage Test : 21kV / 5min.
Partial Discharge : 5pC/10kV
Insulation resistance : Min. 40,000 GΩm(20oC)
Copper wire screen earth fault current : 10kA/s
Bending radius
During installation: 25xOD
Installed: 15xOD
(OD: overall diameter)
CUSTOMER’S OPTIONS
Water-blocking
- Longitudinal water-blocking: Swellable tape
- Radial water-blocking: Aluminum laminated tape
Protection from insect attack
- Chemical add in to over sheath
- Polyamide jacket
- Double brass tape
AS/NZS 1429.1:2006
6.35/11(12)kV - Single core
Nominal Area | Diameter conductor | Nominal thickness insulation | Copper wire screened structure | Nominal Thickness of composite sheath | Approx. Overall Cable Diameter | Approx. Weight of conductor (copper or aluminum conductors) |
| | | | | |
PVC | HDPE | CU | AL |
mm2 | mm | mm | no./mm | mm | mm | mm | Kg/km | Kg/km |
95 | 11.4 | 3.4 | 48 / 1.35 | 1.0 | 1.0 | 28 | 1,910 | 1,330 |
120 | 12.8 | 3.4 | 48 / 1.35 | 1.0 | 1.0 | 29 | 2,150 | 1,430 |
150 | 14.2 | 3.4 | 48 / 1.35 | 1.0 | 1.0 | 31 | 2,430 | 1,530 |
185 | 15.8 | 3.4 | 48 / 1.35 | 1.0 | 1.0 | 32 | 2,790 | 1,670 |
240 | 18.1 | 3.4 | 48 / 1.35 | 1.0 | 1.0 | 35 | 3,360 | 1,880 |
300 | 20.4 | 3.4 | 48 / 1.35 | 1.0 | 1.1 | 37 | 3,960 | 2,100 |
400 | 23.2 | 3.4 | 48 / 1.35 | 1.1 | 1.1 | 40 | 4,800 | 2,420 |
500 | 26.3 | 3.4 | 48 / 1.35 | 1.1 | 1.2 | 45 | 5,930 | 2,870 |
630 | 30.2 | 3.4 | 48 / 1.35 | 1.2 | 1.2 | 49 | 7,340 | 3,380 |
800 | 34.2 | 3.4 | 48 / 1.35 | 1.2 | 1.3 | 53 | 9,040 | 3,960 |