Applied standard
AS/NZS 1429.1:2006
Properties
Rated voltage : 6.35/11(12)kV
AC Voltage Test : 21kV / 5min.
Partial Discharge : 5pC/10kV
Insulation resistance : Min. 40,000 GΩm(20oC)
Copper wire screen earth fault current : 10kA/s
Bending radius
During installation: 25xOD
Installed: 15xOD
(OD: overall diameter)
CUSTOMER’S OPTIONS
Water-blocking
- Longitudinal water-blocking: Swellable tape
- Radial water-blocking: Aluminum laminated tape
Protection from insect attack
- Chemical add in to over sheath
- Polyamide jacket
- Double brass tape
AS/NZS 1429.1:2006
6.35/11(12)kV, Three-core
Nominal Area | Diameter conductor | Nominal thickness insulation | Copper wire screened structure | Nominal Thickness of composite sheath | Approx. Overall Cable Diameter | Approx. Weight of conductor (copper or aluminum conductors) |
| | | | | |
PVC | HDPE | CU | AL |
mm2 | mm | mm | no./mm | mm | mm | mm | Kg/km | Kg/km |
25 | 5.9 | 3.4 | 40 / 0.85 | 1.1 | 1.2 | 42 | 2,330 | - |
35 | 6.9 | 3.4 | 40 / 0.85 | 1.2 | 1.2 | 44 | 2,730 | - |
50 | 8.0 | 3.4 | 40 / 0.85 | 1.2 | 1.3 | 47 | 3,140 | - |
70 | 9.7 | 3.4 | 40 / 0.85 | 1.3 | 1.3 | 51 | 3,900 | 2,650 |
95 | 11.4 | 3.4 | 40 / 0.85 | 1.3 | 1.4 | 54 | 4,790 | 3,050 |
120 | 12.8 | 3.4 | 40 / 0.85 | 1.4 | 1.4 | 58 | 5,630 | 3,430 |
150 | 14.2 | 3.4 | 40 / 0.85 | 1.4 | 1.5 | 61 | 6,470 | 3,760 |
185 | 15.8 | 3.4 | 40 / 0.85 | 1.5 | 1.5 | 64 | 7,670 | 4,270 |
240 | 18.1 | 3.4 | 40 / 0.85 | 1.6 | 1.6 | 70 | 9,580 | 5,100 |
300 | 20.4 | 3.4 | 40 / 0.85 | 1.6 | 1.7 | 76 | 11,470 | 5,840 |
400 | 23.2 | 3.4 | 40 / 0.85 | 1.8 | 1.8 | 82 | 14,190 | 7,050 |