Construction
Core wire (INVAR): Aluminum-clad INVAR Wire
Conductor (XTAL) : Extra Thermal Resistant Aluminum Alloy wire used for continuous allowable temperature up to 230oC
Standard
IEC, ASTM, JCS 1404
Application
XTACIR is normally used to up-rate an existing transmission line by simply replacing the existing conductor without tower modification or reinforcement.
Conductor size
|
Cross-sectional Area
|
Conductor construction
|
Approx. Overall diameter
|
Approx. Overall weight
|
Maximum DC resistance at 20oC
|
Minimum breaking load
|
Modulus of Elasticity
|
Coefficient of Linear Expansion
|
|
XTAL
|
AL-Clad invar
|
XTAL
|
AL-Clad invar
|
|
|
|
|
Up to transition point temperature
|
Over transition point temperature
|
Up to transition point temperature
|
Over transition point temperature
|
mm2
|
mm2
|
mm2
|
No.xmm
|
No.xmm
|
mm
|
kg/km
|
Ω/km
|
kN
|
Kgf/ mm2
|
x10-6/oC
|
160
|
153.1
|
49.48
|
24/2.85
|
7/3.0
|
17.3
|
774.6
|
0.1840
|
68.6
|
83.8
|
152.0
|
14.5
|
10.8
|
200
|
187.0
|
63.55
|
24/3.15
|
7/3.4
|
19.2
|
968.6
|
0.1500
|
83.4
|
84.7
|
152.0
|
14.2
|
10.8
|
240
|
224.4
|
79.38
|
24/3.45
|
7/3.8
|
21.2
|
1,184
|
0.1240
|
102.8
|
85.4
|
152.0
|
14.0
|
10.8
|
320
|
309.1
|
79.38
|
24/4.05
|
7/3.8
|
23.8
|
1,418
|
0.0924
|
114.3
|
80.2
|
152.0
|
15.5
|
10.8
|
400
|
381.6
|
101.6
|
24/4.50
|
7/4.3
|
26.6
|
1,776
|
0.0747
|
139.8
|
80.8
|
152.0
|
15.4
|
10.8
|
600
|
572.0
|
137.5
|
28/5.10
|
7/5.0
|
32.2
|
2,556
|
0.0503
|
197.1
|
79.3
|
152.0
|
15.8
|
10.8
|