Construction
Core Wire(AW) : Aluminum-clad Steel Wire
Conductor (Hi-TAL) : High Tensile Strength Thermal Resistant Aluminum Alloy Wire used for continuous allowable temperature up to 150oC
Characteristics
Excellent rustless characteristics
Low sag & High tension characteristics
High current carrying capacity characteristics
Standard
IEC, ASTM, LSC Standard, JCS1363
Application
Hi-TACSR/AW is used for electric power transmission lines. River-crossing area, seaside district and over seas area, long span, mountain area etc.
Hi-TACSR/AW (20.3% IACS Conductivity AW, 135kgf/mm2)
Conductor size | Section Area | Conductor Construction | Approx. Overall diameter | Approx. Overall weight | Maximum DC resistance at 20oC | Modulus of Elasticity | Coefficient of Linear Expansion | Minimum breaking load | Current Carrying Capacity |
| Hi-TAL | AW | Hi-TAL | AW | | | | | | | |
mm2 | mm2 | mm2 | No.xmm | No.xmm | mm | kg/km | Ω/km | Kgf/ mm2 | x10-6/oC | Kgf | A |
79 | 79.26 | 46.24 | 12 x 2.9 | 7 x 2.9 | 14.5 | 521.4 | 0.331 | 9,930 | 16.9 | 7400 | 471 |
97 | 96.5 | 56.29 | 12 x 3.2 | 7 x 3.2 | 16 | 634.9 | 0.272 | 9,930 | 16.9 | 9010 | 536 |
120 | 115.5 | 67.35 | 12 x 3.5 | 7 x 3.5 | 17.5 | 759.7 | 0.227 | 9,930 | 16.9 | 10750 | 605 |
150 | 150.8 | 87.99 | 12 x 4.0 | 7 x 4.0 | 20 | 992.5 | 0.173 | 9,930 | 16.9 | 14000 | 728 |
120 | 124.7 | 29.09 | 30 x 2.3 | 7 x 2.3 | 16.1 | 536.5 | 0.237 | 8,260 | 19.2 | 6420 | 598 |
160 | 159.3 | 37.16 | 30 x 2.6 | 7 x 2.6 | 18.2 | 685 | 0.186 | 8,260 | 19.2 | 8140 | 704 |
240 | 241.3 | 56.29 | 30 x 3.2 | 7 x 3.2 | 22.4 | 1038 | 0.123 | 8,260 | 19.2 | 12210 | 928 |
330 | 326.8 | 52.84 | 26 x 4.0 | 7 x 3.1 | 25.3 | 1252 | 0.0927 | 7,790 | 20.1 | 13560 | 1114 |
410 | 413.4 | 67.35 | 26 x 4.5 | 7 x 3.5 | 28.5 | 1587 | 0.0732 | 7,800 | 20 | 16710 | 1306 |
610 | 612.4 | 79.38 | 54 x 3.8 | 7 x 3.8 | 34.2 | 2219 | 0.0501 | 7,570 | 20.5 | 23200 | 1649 |
680 | 684.5 | 46.24 | 45x 4.4 | 7 x 2.9 | 35.1 | 2201 | 0.0458 | 7,090 | 21.5 | 19710 | 1736 |
810 | 814.5 | 56.29 | 45 x 4.8 | 7 x 3.2 | 38.4 | 2628 | 0.0385 | 7,100 | 21.5 | 23630 | 1950 |
1160 | 1163 | 96.95 | 84 x 4.2 | 7 x 4.2 | 46.2 | 3872 | 0.0269 | 7,220 | 21.2 | 35750 | 2507 |
1520 | 1520 | 126.7 | 84 x 4.8 | 7 x 4.8 | 52.8 | 5060 | 0.0206 | 7,210 | 21.2 | 46670 | 2964 |
Hi-TACSR/AW (23% IACS Conductivity AW, 130kgf/mm2)
Conductor size | Section Area | Conductor Construction | Approx. Overall diameter | Approx. Overall weight | Maximum DC resistance at 20oC | Modulus of Elasticity | Coefficient of Linear Expansion | Minimum breaking load | Current Carrying Capacity |
| Hi-TAL | AW | Hi-TAL | AW | | | | | | | |
mm2 | mm2 | mm2 | No.xmm | No.xmm | mm | kg/km | Ω/km | Kgf/ mm2 | x10-6/oC | Kgf | A |
79 | 79.26 | 46.24 | 12 x 2.9 | 7 x 2.9 | 14.5 | 509.3 | 0.323 | 9,710 | 17.2 | 7,190 | 476 |
97 | 96.5 | 56.29 | 12 x 3.2 | 7 x 3.2 | 16 | 620.2 | 0.265 | 9,710 | 17.2 | 8,750 | 543 |
120 | 115.5 | 67.35 | 12 x 3.5 | 7 x 3.5 | 17.5 | 742 | 0.222 | 9,710 | 17.2 | 10,430 | 612 |
150 | 150.8 | 87.99 | 12 x 4.0 | 7 x 4.0 | 20 | 969.4 | 0.169 | 9,710 | 17.2 | 13,560 | 734 |
120 | 124.7 | 29.09 | 30 x 2.3 | 7 x 2.3 | 16.1 | 528.9 | 0.235 | 8,150 | 19.4 | 6,290 | 601 |
160 | 159.3 | 37.16 | 30 x 2.6 | 7 x 2.6 | 18.2 | 675.7 | 0.184 | 8,150 | 19.4 | 7,970 | 707 |
240 | 241.3 | 56.29 | 30 x 3.2 | 7 x 3.2 | 22.4 | 1,024 | 0.122 | 8,150 | 19.4 | 11,960 | 932 |
330 | 326.8 | 52.84 | 26 x 4.0 | 7 x 3.1 | 25.3 | 1,238 | 0.092 | 7,710 | 20.2 | 13,320 | 1,118 |
410 | 413.4 | 67.35 | 26 x 4.5 | 7 x 3.5 | 28.5 | 1,570 | 0.0727 | 7,720 | 20.2 | 16,390 | 1,310 |
610 | 612.4 | 79.38 | 54 x 3.8 | 7 x 3.8 | 34.2 | 2,198 | 0.0497 | 7,500 | 20.7 | 22,820 | 1,656 |
680 | 684.5 | 46.24 | 45 x 4.4 | 7 x 2.9 | 35.1 | 2,189 | 0.0457 | 7,050 | 21.6 | 19,510 | 1,738 |
810 | 814.5 | 56.29 | 45 x 4.8 | 7 x 3.2 | 38.4 | 2,613 | 0.0384 | 7,060 | 21.6 | 23,380 | 1,952 |
1,160 | 1,163 | 96.95 | 84 x 4.2 | 7 x 4.2 | 46.2 | 3,847 | 0.0267 | 7,170 | 21.4 | 35,310 | 2,516 |
1,520 | 1,520 | 126.7 | 84 x 4.8 | 7 x 4.8 | 52.8 | 5,027 | 0.0205 | 7,170 | 21.4 | 46,100 | 2,971 |
Hi-TACSR/AW (23% IACS Conductivity AW, 125kgf/mm2)
Conductor size | Section Area | Conductor Construction | Approx. Overall diameter | Approx. Overall weight | Maximum DC resistance at 20oC | Modulus of Elasticity | Coefficient of Linear Expansion | Minimum breaking load | Current Carrying Capacity |
| Hi-TAL | AW | Hi-TAL | AW | | | | | | | |
mm2 | mm2 | mm2 | No.xmm | No.xmm | mm | kg/km | Ω/km | Kgf/ mm2 | x10-6/oC | Kgf | A |
79 | 79.26 | 46.24 | 12 x 2.9 | 7 x 2.9 | 14.5 | 509.3 | 0.323 | 9,710 | 17.2 | 6,990 | 476 |
97 | 96.5 | 56.29 | 12 x 3.2 | 7 x 3.2 | 16 | 620.2 | 0.265 | 9,710 | 17.2 | 8,500 | 543 |
120 | 115.5 | 67.35 | 12 x 3.5 | 7 x 3.5 | 17.5 | 742 | 0.222 | 9,710 | 17.2 | 10,120 | 612 |
150 | 150.8 | 87.99 | 12 x 4.0 | 7 x 4.0 | 20 | 969.4 | 0.169 | 9,710 | 17.2 | 13,190 | 734 |
120 | 124.7 | 29.09 | 30 x 2.3 | 7 x 2.3 | 16.1 | 528.9 | 0.235 | 8,150 | 19.4 | 6,160 | 601 |
160 | 159.3 | 37.16 | 30 x 2.6 | 7 x 2.6 | 18.2 | 675.7 | 0.184 | 8,150 | 19.4 | 7,800 | 707 |
240 | 241.3 | 56.29 | 30 x 3.2 | 7 x 3.2 | 22.4 | 1,024 | 0.122 | 8,150 | 19.4 | 11,710 | 932 |
330 | 326.8 | 52.84 | 26 x 4.0 | 7 x 3.1 | 25.3 | 1,238 | 0.092 | 7,710 | 20.2 | 13,080 | 1,118 |
410 | 413.4 | 67.35 | 26 x 4.5 | 7 x 3.5 | 28.5 | 1,570 | 0.0727 | 7,720 | 20.2 | 16,080 | 1,310 |
610 | 612.4 | 79.38 | 54 x 3.8 | 7 x 3.8 | 34.2 | 2,198 | 0.0497 | 7,500 | 20.7 | 22,510 | 1,656 |
680 | 684.5 | 46.24 | 45 x 4.4 | 7 x 2.9 | 35.1 | 2,189 | 0.0457 | 7,050 | 21.6 | 19,300 | 1,738 |
810 | 814.5 | 56.29 | 45 x 4.8 | 7 x 3.2 | 38.4 | 2,613 | 0.0384 | 7,060 | 21.6 | 23,130 | 1,952 |
1,160 | 1,163 | 96.95 | 84 x 4.2 | 7 x 4.2 | 46.2 | 3,847 | 0.0267 | 7,170 | 21.4 | 34,860 | 2,516 |
1,520 | 1,520 | 126.7 | 84 x 4.8 | 7 x 4.8 | 52.8 | 5,027 | 0.0205 | 7,170 | 21.4 | 45,540 | 2,971 |