Construction
Core Wire (INVAR) : Aluminum-clad INVAR Wire/High Tensile Strength Aluminum-clad INVAR Wire
Conductor (STAL) : Super Thermal Resistant Aluminum Alloy Wire used for continuous allowable temperature up to 210°C
Standard
IEC, ASTM, LSC Standard, JCS 1405
•Double current carrying capacity of the same size ACSR
•No limitation for application area: Heavy wind, snow & galloping area
•Equivalent Sag-tension properties to conventional ACSR
•No modification & reinforcement on existing tower
•Easy installation with same method & equipments as ACSR’s
•Low cost and short construction period
•Proved long-term reliability
Application
Hi-TACSR/AW is used for electric power transmission lines. River-crossing area, seaside district and over seas area, long span, mountain area etc.
STACIR/AW
Size
|
Section Area
|
Conductor Construction
|
Approx. Overall diameter
|
Approx. Overall weight
|
Maximum DC resistance at 20oC
|
Modulus of Elasticity
|
Coefficient of Linear Expansion
|
Ultimate Tensile Strength
|
Current Carrying Capacity
|
|
STAL
|
AL-INVAR
|
STAL
|
AL-INVAR
|
mm2
|
mm2
|
mm2
|
No.xmm
|
No.xmm
|
mm
|
kg/km
|
Ω/km
|
Kgf/ mm2
|
x10-6/oC
|
Kgf
|
A
|
160
|
159.30
|
37.16
|
30 x 2.60
|
7 x 2.60
|
18.20
|
441.7
|
0.1745
|
6,140
|
16.0
|
6,140
|
909
|
240
|
241.30
|
56.29
|
30 x 3.20
|
7 x 3.20
|
22.40
|
669.1
|
0.1159
|
9,170
|
16.0
|
9,170
|
1,203
|
330
|
326.80
|
52.84
|
26 x 4.00
|
7 x 3.10
|
25.30
|
905.1
|
0.0869
|
10,000
|
17.5
|
10,000
|
1,452
|
410
|
413.40
|
67.35
|
26 x 4.50
|
7 x 3.50
|
28.50
|
1,145.5
|
0.0686
|
12,720
|
17.5
|
12,720
|
1,708
|
480 (Rail)
|
483.84
|
33.54
|
45 x 3.70
|
7 x 2.47
|
29.61
|
1,340.7
|
0.0600
|
10,500
|
20.0
|
10,500
|
1,812
|
480(Cardinal)
|
484.52
|
62.81
|
54 x 3.38
|
7 x 3.38
|
30.42
|
1,343.5
|
0.0591
|
13,280
|
18.3
|
13,280
|
1,846
|
Hi-STACIR/AW
Size
|
Section Area
|
Conductor Construction
|
Approx. Overall diameter
|
Approx. Overall weight
|
Maximum DC resistance at 20oC
|
Modulus of Elasticity
|
Coefficient of Linear Expansion
|
Ultimate Tensile Strength
|
Current Carrying Capacity
|
|
STAL
|
Hi-AL-INVAR
|
STAL
|
Hi-AL-INVAR
|
mm2
|
mm2
|
mm2
|
No.xmm
|
No.xmm
|
mm
|
kg/km
|
Ω/km
|
Kgf/ mm2
|
x10-6/oC
|
Kgf
|
A
|
160
|
159.30
|
37.16
|
30/2.60
|
7/2.60
|
18.20
|
706.9
|
0.1745
|
8,040
|
16.0
|
6,500
|
909
|
240
|
241.30
|
56.29
|
30/3.20
|
7/3.20
|
22.40
|
1070.8
|
0.1159
|
8,040
|
16.0
|
9,700
|
1,203
|
330
|
326.80
|
52.84
|
26/4.00
|
7/3.10
|
25.30
|
1282.1
|
0.0869
|
7,580
|
17.5
|
10,500
|
1,452
|
410
|
413.40
|
67.35
|
26/4.50
|
7/3.50
|
28.50
|
1626.1
|
0.0686
|
7,590
|
17.5
|
13,300
|
1,708
|
480 (Rail)
|
483.84
|
33.54
|
45/3.70
|
7/2.47
|
29.61
|
1580.0
|
0.0600
|
6,900
|
20.0
|
11,000
|
1,812
|
480(Cardinal)
|
484.52
|
62.81
|
54/3.38
|
7/3.38
|
30.42
|
1795.7
|
0.0591
|
7,470
|
18.3
|
13,800
|
1,846
|